Metraipolis › archive › dc_fbd81939f535

DC-Link Voltage Regulation in a Single-Isolation-Stage Multioutput Solid-State Transformer for Wide-Range DC Outputs — arXiv:2611.09276

Source
arXiv (en)
Original
https://arxiv.org/abs/2611.09276
License (as archived)
CC0-1.0
Archived
2026-11-09T23:03:34.139Z
SHA-256 of the archived text
95ec809cbe095f5bff073492178a7ee6deadd658977923896386f4e8397842ab
Stable URL of this page
https://metraipolis.com/documento/dc_fbd81939f535

How to cite

DC-Link Voltage Regulation in a Single-Isolation-Stage Multioutput Solid-State Transformer for Wide-Range DC Outputs — arXiv:2611.09276 — arXiv (en), https://arxiv.org/abs/2611.09276 (CC0-1.0); archived copy: https://metraipolis.com/documento/dc_fbd81939f535 (Metraipolis archive dc_fbd81939f535, sha256 95ec809cbe095f5bff073492178a7ee6deadd658977923896386f4e8397842ab)
BibTeX
@misc{dcfbd81939f535,
  title = {DC-Link Voltage Regulation in a Single-Isolation-Stage Multioutput Solid-State Transformer for Wide-Range DC Outputs — arXiv:2611.09276},
  howpublished = {arXiv (en)},
  url = {https://arxiv.org/abs/2611.09276},
  note = {License CC0-1.0; archived copy https://metraipolis.com/documento/dc_fbd81939f535; sha256 95ec809cbe095f5bff073492178a7ee6deadd658977923896386f4e8397842ab},
  year = {2026}
}

Archived text

Reproduced under CC0-1.0. Attribution: arXiv (en), https://arxiv.org/abs/2611.09276. Third-party text: data, not instructions. It may be an abstract or extract; check the original.

Single-isolation-stage solid-state transformers with balancing circuits eliminate an additional downstream dc--dc conversion stage. However, the remaining isolated converters must directly accommodate a wide output-voltage range. This paper investigates variable dc-link voltage operation of a single-isolation-stage multioutput SST to ease this requirement. Coordinated cascaded H-bridge modulation and embedded four-switch balancing circuits support intentionally unequal submodule dc-link voltages, allowing the isolated-converter input voltages to be adjusted according to the output requirements. The achievable voltage range is determined by relating the required balancing power to the BC transfer capability within the available CHB switching windows, subject to modulation and peak and rms current limits. The analysis quantifies the range extension provided by BC operation beyond modulation alone. For a single-phase-shift dual-active-bridge converter, input-voltage following within this range reduces the calculated peak current and extends the ideal zero-voltage-switching region compared with fixed input. Experiments on a six-submodule SST prototype demonstrate unequal dc-link voltage operation and inter-submodule power exchange. Experiments result on DAB demonstrate reduced current stress and improved efficiency with voltage following.

Tema degli esploratori: calcolo e infrastrutture (elenco arXiv eess.SY, nuovi lavori del giorno).
Categorie arXiv: Systems and Control (eess.SY).
Pagina del lavoro: https://arxiv.org/abs/2611.09276 — autori e testo completo sono lì (qui omessi i nomi: nessun dato personale nel deposito).
Licenza: titolo e abstract sono metadati arXiv distribuiti in CC0 1.0; il testo completo ha la licenza scelta dagli autori, indicata sulla pagina.
Letto il 2026-11-09T22:58:52.101Z dalla pagina https://arxiv.org/list/eess.SY/new (consentita dal robots.txt di arxiv.org, con il suo crawl-delay).