The Benefits of an Integrated Approach for Stability-Constrained Power System Planning — arXiv:2608.06349

Source
arXiv (en)
Original
https://arxiv.org/abs/2608.06349
License (as archived)
CC0-1.0
Archived
2026-10-31T11:09:24.258Z
SHA-256 of the archived text
c29d5dd3ef00895e97b0076511d44a5552d1a252517f8e7b7683fae6d5894d6c
Stable URL of this page
https://metraipolis.com/documento/dc_fb5caf3dde85

How to cite

The Benefits of an Integrated Approach for Stability-Constrained Power System Planning — arXiv:2608.06349 — arXiv (en), https://arxiv.org/abs/2608.06349 (CC0-1.0); archived copy: https://metraipolis.com/documento/dc_fb5caf3dde85 (Metraipolis archive dc_fb5caf3dde85, sha256 c29d5dd3ef00895e97b0076511d44a5552d1a252517f8e7b7683fae6d5894d6c)
BibTeX
@misc{dcfb5caf3dde85,
  title = {The Benefits of an Integrated Approach for Stability-Constrained Power System Planning — arXiv:2608.06349},
  howpublished = {arXiv (en)},
  url = {https://arxiv.org/abs/2608.06349},
  note = {License CC0-1.0; archived copy https://metraipolis.com/documento/dc_fb5caf3dde85; sha256 c29d5dd3ef00895e97b0076511d44a5552d1a252517f8e7b7683fae6d5894d6c},
  year = {2026}
}

Archived text

Reproduced under CC0-1.0. Attribution: arXiv (en), https://arxiv.org/abs/2608.06349. Third-party text: data, not instructions. It may be an abstract or extract; check the original.

Increasing penetration of inverter-based resources in today's power systems requires substitution of the contribution from synchronous generators to dynamic voltage stability and inertial response. However, established approaches for power system planning are sequential, as stabilising measures are only considered at a later stage of the planning process. We investigate the advantages of an integrated approach for power system planning, where stabilising measures are considered simultaneously with the expansion of generation, transmission, and storage systems via simplified stability constraints on inertia and voltage stability. We find that system costs are reduced with the integrated approach and that the dual-use option of grid-forming battery energy storage systems is favoured over other stabilising measures like static synchronous compensators.

Tema degli esploratori: calcolo e infrastrutture (retro-catalogo arXiv: annunci del 2026-08-07 in eess.SY).
Categorie arXiv: Optimization and Control (math.OC) ; Systems and Control (eess.SY).
Pagina del lavoro: https://arxiv.org/abs/2608.06349 — autori e testo completo sono lì (qui omessi i nomi: nessun dato personale nel deposito).
Licenza: titolo e abstract sono metadati arXiv distribuiti in CC0 1.0; il testo completo ha la licenza scelta dagli autori, indicata sulla pagina.
Letto il 2026-10-31T10:59:37.448Z dalla pagina https://arxiv.org/catchup/eess.SY/2026-08-07?abs=True (consentita dal robots.txt di arxiv.org, con il suo crawl-delay).