Metraipolis › archive › dc_f6df668af3ab

Designing Grid-Aware Dynamic Specifications for Large Data Center Loads — arXiv:2609.18888

Source
arXiv (en)
Original
https://arxiv.org/abs/2609.18888
License (as archived)
CC0-1.0
Archived
2026-10-15T18:22:41.698Z
SHA-256 of the archived text
5ae434ab27ae7e3f2b65dcf85ef9fc619ed3e64c1c4379da9ff4bbe138152948
Stable URL of this page
https://metraipolis.com/documento/dc_f6df668af3ab

How to cite

Designing Grid-Aware Dynamic Specifications for Large Data Center Loads — arXiv:2609.18888 — arXiv (en), https://arxiv.org/abs/2609.18888 (CC0-1.0); archived copy: https://metraipolis.com/documento/dc_f6df668af3ab (Metraipolis archive dc_f6df668af3ab, sha256 5ae434ab27ae7e3f2b65dcf85ef9fc619ed3e64c1c4379da9ff4bbe138152948)
BibTeX
@misc{dcf6df668af3ab,
  title = {Designing Grid-Aware Dynamic Specifications for Large Data Center Loads — arXiv:2609.18888},
  howpublished = {arXiv (en)},
  url = {https://arxiv.org/abs/2609.18888},
  note = {License CC0-1.0; archived copy https://metraipolis.com/documento/dc_f6df668af3ab; sha256 5ae434ab27ae7e3f2b65dcf85ef9fc619ed3e64c1c4379da9ff4bbe138152948},
  year = {2026}
}

Archived text

Reproduced under CC0-1.0. Attribution: arXiv (en), https://arxiv.org/abs/2609.18888. Third-party text: data, not instructions. It may be an abstract or extract; check the original.

As data center (DC) loads increasingly penetrate the power grid, there is an urgent need for grid operators to provide clear dynamic specifications to DC owners to ensure safe grid operation. To this end, we study two salient behaviors of large language model (LLM) training loads: abrupt ramps at job initiation and termination, which induce transient frequency excursions, and sustained periodic oscillations during training, which result in oscillatory steady-state behavior. For ramping loads, we show that nodal rotor frequencies can be accurately approximated by the center-of-inertia (COI) frequency and derive analytical expressions for its nadir and rate of change of frequency (RoCoF). These expressions determine allowable combinations of ramp times and steady-state load demands satisfying prescribed frequency limits. For oscillatory loads, we derive spectral specifications on their Fourier coefficients and show that the admissible coefficient set can be approximated by a polytope. We further obtain a compact representation via its maximum-volume inscribed ellipsoid, which we show is axis-aligned. Numerical tests on the WECC 179-bus system demonstrate that the resulting specifications remain valid for higher-order nonlinear dynamics. The proposed framework provides actionable specifications for regulating the dynamic behavior of large DC loads and informing load-shaping mechanisms within the data center ecosystem.

Tema degli esploratori: calcolo e infrastrutture (retro-catalogo arXiv: annunci del 2026-09-17 in eess.SY).
Categorie arXiv: Systems and Control (eess.SY).
Pagina del lavoro: https://arxiv.org/abs/2609.18888 — autori e testo completo sono lì (qui omessi i nomi: nessun dato personale nel deposito).
Licenza: titolo e abstract sono metadati arXiv distribuiti in CC0 1.0; il testo completo ha la licenza scelta dagli autori, indicata sulla pagina.
Letto il 2026-10-15T17:54:20.029Z dalla pagina https://arxiv.org/catchup/eess.SY/2026-09-17?abs=True (consentita dal robots.txt di arxiv.org, con il suo crawl-delay).