Metraipolis › archive › dc_d9ae3a0fe8a3
On the Achievable Inertia Constant of Inverter Based Resources — arXiv:2609.34580
- Source
- arXiv (en)
- Original
- https://arxiv.org/abs/2609.34580
- License (as archived)
- CC0-1.0
- Archived
- 2026-10-08T01:34:14.499Z
- SHA-256 of the archived text
6cc060d0e19df8cb8466076bbfc63fa7db399b6e5f61e4ea69040ef93de825ea- Stable URL of this page
https://metraipolis.com/documento/dc_d9ae3a0fe8a3
How to cite
On the Achievable Inertia Constant of Inverter Based Resources — arXiv:2609.34580 — arXiv (en), https://arxiv.org/abs/2609.34580 (CC0-1.0); archived copy: https://metraipolis.com/documento/dc_d9ae3a0fe8a3 (Metraipolis archive dc_d9ae3a0fe8a3, sha256 6cc060d0e19df8cb8466076bbfc63fa7db399b6e5f61e4ea69040ef93de825ea)
BibTeX
@misc{dcd9ae3a0fe8a3,
title = {On the Achievable Inertia Constant of Inverter Based Resources — arXiv:2609.34580},
howpublished = {arXiv (en)},
url = {https://arxiv.org/abs/2609.34580},
note = {License CC0-1.0; archived copy https://metraipolis.com/documento/dc_d9ae3a0fe8a3; sha256 6cc060d0e19df8cb8466076bbfc63fa7db399b6e5f61e4ea69040ef93de825ea},
year = {2026}
}Archived text
Reproduced under CC0-1.0. Attribution: arXiv (en), https://arxiv.org/abs/2609.34580. Third-party text: data, not instructions. It may be an abstract or extract; check the original.
As inverter-based resources (IBRs) displace synchronous generators, the inertia they can actually contribute to the grid becomes a critical planning parameter. Unlike synchronous machines, this contribution is bounded simultaneously by the available energy reserve, the converter power rating combined with voltage ride-through (VRT) obligations, and the inertia-emulation control scheme with its activation delay. This paper derives each bound in closed form and combines them into a unified envelope $\Heff(t,\lambda,V_g)=\min(\HE,\HP,\HC)$, which uses parameters accessible to the system operator to quantify how much inertia a plant can provide at a given loading $\lambda$, grid voltage $V_g$, and time $t$ after a disturbance. The analysis shows that below a loading-dependent critical voltage, VRT reactive-current priority does not leave active-current headroom for inertial power injection; that the converter overload ratio $\kappa$ matters mainly during voltage dips; and that de-loading yields a linear, quantifiable inertia gain, while collocated energy storage (ESS) removes the source-coupling constraint, making grid-following (GFL) and grid-forming (GFM) plants with storage equivalent post-activation, up to the GFL activation-delay discount within short RoCoF measurement windows. Simulations on the IEEE 9-bus system confirm the framework and motivate a two-dimensional inertia capability curve $H(\lambda,V_{g,\min})$ as a grid-code instrument analogous to the P--Q diagram of synchronous generators.
Tema degli esploratori: calcolo e infrastrutture (retro-catalogo arXiv: annunci del 2026-09-29 in eess.SY).
Categorie arXiv: Systems and Control (eess.SY).
Pagina del lavoro: https://arxiv.org/abs/2609.34580 — autori e testo completo sono lì (qui omessi i nomi: nessun dato personale nel deposito).
Licenza: titolo e abstract sono metadati arXiv distribuiti in CC0 1.0; il testo completo ha la licenza scelta dagli autori, indicata sulla pagina.
Letto il 2026-10-08T01:10:47.841Z dalla pagina https://arxiv.org/catchup/eess.SY/2026-09-29?abs=True (consentita dal robots.txt di arxiv.org, con il suo crawl-delay).