Metraipolis › archive › dc_d71624024707

An Optimal Power-Flow Grouping Topology for Single-Isolation-Stage Multi-Output Solid-State Transformers — arXiv:2611.09305

Source
arXiv (en)
Original
https://arxiv.org/abs/2611.09305
License (as archived)
CC0-1.0
Archived
2026-11-09T23:03:34.198Z
SHA-256 of the archived text
eeb09d1e1c4dd5a020986737f56df61d59368b46b12f441c6ce80bf8c4f2a432
Stable URL of this page
https://metraipolis.com/documento/dc_d71624024707

How to cite

An Optimal Power-Flow Grouping Topology for Single-Isolation-Stage Multi-Output Solid-State Transformers — arXiv:2611.09305 — arXiv (en), https://arxiv.org/abs/2611.09305 (CC0-1.0); archived copy: https://metraipolis.com/documento/dc_d71624024707 (Metraipolis archive dc_d71624024707, sha256 eeb09d1e1c4dd5a020986737f56df61d59368b46b12f441c6ce80bf8c4f2a432)
BibTeX
@misc{dcd71624024707,
  title = {An Optimal Power-Flow Grouping Topology for Single-Isolation-Stage Multi-Output Solid-State Transformers — arXiv:2611.09305},
  howpublished = {arXiv (en)},
  url = {https://arxiv.org/abs/2611.09305},
  note = {License CC0-1.0; archived copy https://metraipolis.com/documento/dc_d71624024707; sha256 eeb09d1e1c4dd5a020986737f56df61d59368b46b12f441c6ce80bf8c4f2a432},
  year = {2026}
}

Archived text

Reproduced under CC0-1.0. Attribution: arXiv (en), https://arxiv.org/abs/2611.09305. Third-party text: data, not instructions. It may be an abstract or extract; check the original.

Electric-vehicle dc fast-charging stations and data centers require multiple high-power dc outputs with independently varying demands. Conventional multi-output solid-state transformers typically establish a common dc bus and use downstream dc/dc converters for port-level regulation and, where required, galvanic isolation. A single-isolation-stage solid-state transformer can eliminate this additional high-power interface stage by directly forming multiple isolated outputs from its submodule dc/dc stages. However, because one submodule is generally insufficient for an individual output port, multiple submodules must be connected in parallel, while inter-submodule balancing circuits redistribute power under unbalanced loading. The submodule grouping therefore determines the internal balancing-power paths. Sequential grouping can create long transfer paths and accumulated balancing power, increasing current stress and losses. This paper proposes an optimal power-flow grouping topology that interleaves submodules assigned to different output ports, thereby localizing power redistribution and reducing the power processed by the balancing circuits. Analytical models quantify the required balancing power and its reduction relative to sequential grouping. A coordinated submodule-bypass strategy is also developed, and the remaining output-power capability under different fault scenarios is evaluated. A six-submodule prototype validates the proposed topology. Under the same highly unbalanced operating conditions, the proposed topology reduces the maximum submodule dc-link voltage difference by 63\% and the peak balancing current by 14.5%, while improving the measured efficiency by approximately 5.6% at rated power. Stable post-fault operation is also experimentally demonstrated.

Tema degli esploratori: calcolo e infrastrutture (elenco arXiv eess.SY, nuovi lavori del giorno).
Categorie arXiv: Systems and Control (eess.SY).
Pagina del lavoro: https://arxiv.org/abs/2611.09305 — autori e testo completo sono lì (qui omessi i nomi: nessun dato personale nel deposito).
Licenza: titolo e abstract sono metadati arXiv distribuiti in CC0 1.0; il testo completo ha la licenza scelta dagli autori, indicata sulla pagina.
Letto il 2026-11-09T22:58:52.102Z dalla pagina https://arxiv.org/list/eess.SY/new (consentita dal robots.txt di arxiv.org, con il suo crawl-delay).