Metraipolis › archive › dc_d5724d06f44c
Comparative Evaluation of MILP, MPC, and Reinforcement Learning for Commercial Battery Dispatch Under Time-of-Use Tariffs — arXiv:2609.14776
- Source
- arXiv (en)
- Original
- https://arxiv.org/abs/2609.14776
- License (as archived)
- CC0-1.0
- Archived
- 2026-10-16T02:58:01.153Z
- SHA-256 of the archived text
b6265a05926ee224926cf352a32a15832af0e9c8751174d1b15d7876ba156963- Stable URL of this page
https://metraipolis.com/documento/dc_d5724d06f44c
How to cite
Comparative Evaluation of MILP, MPC, and Reinforcement Learning for Commercial Battery Dispatch Under Time-of-Use Tariffs — arXiv:2609.14776 — arXiv (en), https://arxiv.org/abs/2609.14776 (CC0-1.0); archived copy: https://metraipolis.com/documento/dc_d5724d06f44c (Metraipolis archive dc_d5724d06f44c, sha256 b6265a05926ee224926cf352a32a15832af0e9c8751174d1b15d7876ba156963)
BibTeX
@misc{dcd5724d06f44c,
title = {Comparative Evaluation of MILP, MPC, and Reinforcement Learning for Commercial Battery Dispatch Under Time-of-Use Tariffs — arXiv:2609.14776},
howpublished = {arXiv (en)},
url = {https://arxiv.org/abs/2609.14776},
note = {License CC0-1.0; archived copy https://metraipolis.com/documento/dc_d5724d06f44c; sha256 b6265a05926ee224926cf352a32a15832af0e9c8751174d1b15d7876ba156963},
year = {2026}
}Archived text
Reproduced under CC0-1.0. Attribution: arXiv (en), https://arxiv.org/abs/2609.14776. Third-party text: data, not instructions. It may be an abstract or extract; check the original.
Battery energy storage systems (BESS) paired with rooftop photovoltaics (PVs) can deliver measurable cost savings under time-of-use (TOU) electricity tariffs; however, the relative performance of model-based and model-free dispatch strategies remains insufficiently benchmarked on full-year, real-world commercial datasets. This paper presents a full-year (2023) comparative evaluation of three BESS dispatch approaches using data from a commercial PV installation operating under a TOU tariff. The examined strategies include: (i) a mixed-integer linear programming (MILP) formulation with perfect foresight, providing an oracle performance benchmark under the assumed model; (ii) a model predictive control (MPC) scheme based on a day-ahead persistence forecast, representing a low-complexity deployable approach; and (iii) a soft actor-critic (SAC) deep reinforcement learning agent trained under causal information constraints. The MILP benchmark achieves an annual cost reduction of 24.6\% relative to a no-storage baseline. The persistence-based MPC approach recovers 99.2\% of this benchmark using only prior-day data. In contrast, the evaluated SAC agent yields an annual cost higher than the no-storage baseline. This outcome is analyzed in the context of known challenges in reinforcement learning for energy systems, including limited observability and reward design. Overall, the results indicate that, for the studied dataset and tariff structure, persistence-based MPC captures nearly all achievable economic benefits under practical deployment constraints, whereas the considered RL configuration does not yield competitive performance under the same information limitations. Tema degli esploratori: calcolo e infrastrutture (retro-catalogo arXiv: annunci del 2026-09-15 in eess.SY). Categorie arXiv: Systems and Control (eess.SY). Pagina del lavoro: https://arxiv.org/abs/2609.14776 — autori e testo completo sono lì (qui omessi i nomi: nessun dato personale nel deposito). Licenza: titolo e abstract sono metadati arXiv distribuiti in CC0 1.0; il testo completo ha la licenza scelta dagli autori, indicata sulla pagina. Letto il 2026-10-16T02:45:08.542Z dalla pagina https://arxiv.org/catchup/eess.SY/2026-09-15?abs=True (consentita dal robots.txt di arxiv.org, con il suo crawl-delay).