Metraipolis › archive › dc_d51a71a4d546

Circular Economy Synergies and Trade-offs in Data Centres — arXiv:2608.04571

Source
arXiv (en)
Original
https://arxiv.org/abs/2608.04571
License (as archived)
CC0-1.0
Archived
2026-10-31T11:26:19.707Z
SHA-256 of the archived text
d21d8570a03501fb6346c0eae78f44ffa6c267545e30a984641d1bb7cdeff423
Stable URL of this page
https://metraipolis.com/documento/dc_d51a71a4d546

How to cite

Circular Economy Synergies and Trade-offs in Data Centres — arXiv:2608.04571 — arXiv (en), https://arxiv.org/abs/2608.04571 (CC0-1.0); archived copy: https://metraipolis.com/documento/dc_d51a71a4d546 (Metraipolis archive dc_d51a71a4d546, sha256 d21d8570a03501fb6346c0eae78f44ffa6c267545e30a984641d1bb7cdeff423)
BibTeX
@misc{dcd51a71a4d546,
  title = {Circular Economy Synergies and Trade-offs in Data Centres — arXiv:2608.04571},
  howpublished = {arXiv (en)},
  url = {https://arxiv.org/abs/2608.04571},
  note = {License CC0-1.0; archived copy https://metraipolis.com/documento/dc_d51a71a4d546; sha256 d21d8570a03501fb6346c0eae78f44ffa6c267545e30a984641d1bb7cdeff423},
  year = {2026}
}

Archived text

Reproduced under CC0-1.0. Attribution: arXiv (en), https://arxiv.org/abs/2608.04571. Third-party text: data, not instructions. It may be an abstract or extract; check the original.

This report analyses data centre (DC) sustainability and circularity, revealing existing synergies and trade-offs: The PUE is too coarse, mixing cooling and power provisioning. It wrongly attributes server fan consumption and transformation losses to IT energy. It does not measure compute but infrastructure efficiency, which is already outstanding. Compute energy, however, is exploding. Better energy metrics for DCs would thus cover i) compute efficiency, ii) transformation efficiency, and iii) cooling overhead. Trade-offs exist between cooling energy and water as well as on-site and upstream water: Consuming water on-site lowers the cooling energy, which also lowers the water consumed upstream in power generation. For 'wet' electricity, there is little competition: It is worth spending more on-site energy to save both electricity and related upstream water. For 'dry' electricity, there is a trade-off. Waste heat recovery brings energy circularity but has limited uses and is not the same energy quality, a fact not reflected by current metrics. A better metric would consider the avoided energy through heat recovery instead of the amount recovered. Material circularity can be achieved by interpreting the 9R framework in the context of DCs. Circularity-enhancing measures can be categorised into product design, process design and business models, choice of materials, and operating conditions. Together, they have effects across all circularity levels. The relation between DCs and the power grid is complex. Modern DCs present new challenges for the grid. Mitigation includes battery storage and onsite generation. These measures have, in turn, further consequences, both beneficial and detrimental. They can offer grid flexibility as well as innovations in the field of energy. But they also bring noise, pollution, and GHGs, and compete with the energy sector for resources.

Tema degli esploratori: governance digitale e beni comuni (retro-catalogo arXiv: annunci del 2026-08-06 in cs.CY).
Categorie arXiv: Other Computer Science (cs.OH) ; Computers and Society (cs.CY).