Current-Limiting Control for Fault Ride-Through of LLC-based Solid-State Transformer in Data Centers — arXiv:2608.26595
- Source
- arXiv (en)
- Original
- https://arxiv.org/abs/2608.26595
- License (as archived)
- CC0-1.0
- Archived
- 2026-10-17T22:17:26.877Z
- SHA-256 of the archived text
d67f871a0852db5d37823bbb7e9a6cb18e04fa09766d0c515216525fce6f6a99- Stable URL of this page
https://metraipolis.com/documento/dc_d4dd989d8ce7
How to cite
Current-Limiting Control for Fault Ride-Through of LLC-based Solid-State Transformer in Data Centers — arXiv:2608.26595 — arXiv (en), https://arxiv.org/abs/2608.26595 (CC0-1.0); archived copy: https://metraipolis.com/documento/dc_d4dd989d8ce7 (Metraipolis archive dc_d4dd989d8ce7, sha256 d67f871a0852db5d37823bbb7e9a6cb18e04fa09766d0c515216525fce6f6a99)
BibTeX
@misc{dcd4dd989d8ce7,
title = {Current-Limiting Control for Fault Ride-Through of LLC-based Solid-State Transformer in Data Centers — arXiv:2608.26595},
howpublished = {arXiv (en)},
url = {https://arxiv.org/abs/2608.26595},
note = {License CC0-1.0; archived copy https://metraipolis.com/documento/dc_d4dd989d8ce7; sha256 d67f871a0852db5d37823bbb7e9a6cb18e04fa09766d0c515216525fce6f6a99},
year = {2026}
}Archived text
Reproduced under CC0-1.0. Attribution: arXiv (en), https://arxiv.org/abs/2608.26595. Third-party text: data, not instructions. It may be an abstract or extract; check the original.
Solid-State Transformers (SSTs) are increasingly proposed as the interface between distribution grids and data centers due to flexible power flows and fast dynamic response. However, when a short-circuit fault occurs in a load branch, the SST with a voltage-source-type DC-DC stage is forced to shut down due to fault currents. Therefore, current-limiting strategies are strongly needed to prevent catastrophic equipment damage and cascading blackouts by instantly restricting massive current spikes and offering sufficient currents for protection devices to act at the faulted branch. This paper proposes a coordinated DC load fault-tolerant current-limiting and recovery strategy embedded directly in the control of the SST DC-DC stage, avoiding additional hardware cost. Specifically, the fault mechanism of an example LLC resonant converter is studied. Accordingly, a fault detection framework is implemented, a closed-loop current controller is proposed to limit the DC current to a designated value within microseconds by surging the switching frequency and adjusting the duty cycle, and a ramped recovery stage will then restore the DC bus after the fault isolation without inrush currents. Experiments on an LLC converter prototype have verified the feasibility of the proposed current-limiting strategy, enabling faster and lower-cost fault response suitable for resilient data center power architectures. Tema degli esploratori: calcolo e infrastrutture (retro-catalogo arXiv: annunci del 2026-08-28 in eess.SY). Categorie arXiv: Systems and Control (eess.SY). Pagina del lavoro: https://arxiv.org/abs/2608.26595 — autori e testo completo sono lì (qui omessi i nomi: nessun dato personale nel deposito). Licenza: titolo e abstract sono metadati arXiv distribuiti in CC0 1.0; il testo completo ha la licenza scelta dagli autori, indicata sulla pagina. Letto il 2026-10-17T22:17:01.657Z dalla pagina https://arxiv.org/catchup/eess.SY/2026-08-28?abs=True (consentita dal robots.txt di arxiv.org, con il suo crawl-delay).