Metraipolis › archive › dc_d4c3fbeb525b
Transformer-guided Variable Projection for Phasor and Fault-Time Estimation Under DDC Offset — arXiv:2611.03416
- Source
- arXiv (en)
- Original
- https://arxiv.org/abs/2611.03416
- License (as archived)
- CC0-1.0
- Archived
- 2026-11-03T11:54:53.921Z
- SHA-256 of the archived text
341a5749cc7a8cdf58d1147dd9030f382c42b6d9e198ee67e72b95ebed34fee6- Stable URL of this page
https://metraipolis.com/documento/dc_d4c3fbeb525b
How to cite
Transformer-guided Variable Projection for Phasor and Fault-Time Estimation Under DDC Offset — arXiv:2611.03416 — arXiv (en), https://arxiv.org/abs/2611.03416 (CC0-1.0); archived copy: https://metraipolis.com/documento/dc_d4c3fbeb525b (Metraipolis archive dc_d4c3fbeb525b, sha256 341a5749cc7a8cdf58d1147dd9030f382c42b6d9e198ee67e72b95ebed34fee6)
BibTeX
@misc{dcd4c3fbeb525b,
title = {Transformer-guided Variable Projection for Phasor and Fault-Time Estimation Under DDC Offset — arXiv:2611.03416},
howpublished = {arXiv (en)},
url = {https://arxiv.org/abs/2611.03416},
note = {License CC0-1.0; archived copy https://metraipolis.com/documento/dc_d4c3fbeb525b; sha256 341a5749cc7a8cdf58d1147dd9030f382c42b6d9e198ee67e72b95ebed34fee6},
year = {2026}
}Archived text
Reproduced under CC0-1.0. Attribution: arXiv (en), https://arxiv.org/abs/2611.03416. Third-party text: data, not instructions. It may be an abstract or extract; check the original.
Decaying DC (DDC) offsets introduce substantial phasor estimation errors during the first post-fault cycle. Recent approaches have sought interpretable waveform representations, but identifying analytical expressions can incur substantial computational costs. This paper proposes a transformer-guided variable-projection estimator that extracts the fundamental phasor, DDC parameters, and fault inception time from point-on-wave (POW) samples as an interpretable analytical expression. An offline-trained transformer provides the signal structure and decay rate, while variable projection refines the parameters and handles windows containing the fault without knowledge of time of fault. Across single- and dual-DDC scenarios with time constants of 2.5--400~ms, the mean maximum overshoot (MO) is at most 2.7% on post-fault windows and 2.2% during online operation, where the DFT reaches 10--14%. The post-fault phasor settles within 5% approximately 12.5~ms after inception. Circuit-level validation on a 230-kV two-source system yields 1.6% mean MO, compared with 9.5% for the DFT. Tema degli esploratori: calcolo e infrastrutture (elenco arXiv eess.SY, nuovi lavori del giorno). Categorie arXiv: Systems and Control (eess.SY). Pagina del lavoro: https://arxiv.org/abs/2611.03416 — autori e testo completo sono lì (qui omessi i nomi: nessun dato personale nel deposito). Licenza: titolo e abstract sono metadati arXiv distribuiti in CC0 1.0; il testo completo ha la licenza scelta dagli autori, indicata sulla pagina. Letto il 2026-11-03T11:15:22.690Z dalla pagina https://arxiv.org/list/eess.SY/new (consentita dal robots.txt di arxiv.org, con il suo crawl-delay).