Dynamic Modeling of Transmission Networks, Grid-Following Inverters, and UPS-Based AI Data Centers — arXiv:2611.03279
- Source
- arXiv (en)
- Original
- https://arxiv.org/abs/2611.03279
- License (as archived)
- CC0-1.0
- Archived
- 2026-11-03T19:08:36.250Z
- SHA-256 of the archived text
1f9871986e17c8b9bfd6310daf4947b4d24d326128218054fda395fc360c0b3b- Stable URL of this page
https://metraipolis.com/documento/dc_c7bc0a16d4e5
How to cite
Dynamic Modeling of Transmission Networks, Grid-Following Inverters, and UPS-Based AI Data Centers — arXiv:2611.03279 — arXiv (en), https://arxiv.org/abs/2611.03279 (CC0-1.0); archived copy: https://metraipolis.com/documento/dc_c7bc0a16d4e5 (Metraipolis archive dc_c7bc0a16d4e5, sha256 1f9871986e17c8b9bfd6310daf4947b4d24d326128218054fda395fc360c0b3b)
BibTeX
@misc{dcc7bc0a16d4e5,
title = {Dynamic Modeling of Transmission Networks, Grid-Following Inverters, and UPS-Based AI Data Centers — arXiv:2611.03279},
howpublished = {arXiv (en)},
url = {https://arxiv.org/abs/2611.03279},
note = {License CC0-1.0; archived copy https://metraipolis.com/documento/dc_c7bc0a16d4e5; sha256 1f9871986e17c8b9bfd6310daf4947b4d24d326128218054fda395fc360c0b3b},
year = {2026}
}Archived text
Reproduced under CC0-1.0. Attribution: arXiv (en), https://arxiv.org/abs/2611.03279. Third-party text: data, not instructions. It may be an abstract or extract; check the original.
This document presents dynamic models of a transmission network and average models of power-electronic devices and loads in the synchronous $dq$ frame. We model the network in the positive sequence and its synchronous generators with the classical swing equation and a first-order turbine governor. The power-electronic models cover grid-following inverters and AI data centers. Each inverter has a phase-locked loop, a power controller, and a current controller. Each data center connects to the grid through two step-down transformers. Its low-voltage bus feeds an IT load, an induction-motor cooling load, and a constant-impedance load. A double-conversion uninterruptible power supply (UPS) serves the IT load. We model its rectifier, grid-forming output inverter, battery, and bidirectional DC-DC converter. A measured GPU power trace drives the IT demand. We replace every non-smooth operation with a smooth surrogate. This keeps the discretized model continuously differentiable for the nonlinear solver. We also show how we initialize each model at its power-flow operating point. Tema degli esploratori: calcolo e infrastrutture (elenco arXiv eess.SY, nuovi lavori del giorno). Categorie arXiv: Systems and Control (eess.SY). Pagina del lavoro: https://arxiv.org/abs/2611.03279 — autori e testo completo sono lì (qui omessi i nomi: nessun dato personale nel deposito). Licenza: titolo e abstract sono metadati arXiv distribuiti in CC0 1.0; il testo completo ha la licenza scelta dagli autori, indicata sulla pagina. Letto il 2026-11-03T18:25:37.830Z dalla pagina https://arxiv.org/list/eess.SY/new (consentita dal robots.txt di arxiv.org, con il suo crawl-delay).