Metraipolis › archive › dc_b749e5f0e158

A Novel Open Phase Detection Method with Synchronized Phasors for Distribution Systems — arXiv:2608.22466

Source
arXiv (en)
Original
https://arxiv.org/abs/2608.22466
License (as archived)
CC0-1.0
Archived
2026-10-18T10:09:16.309Z
SHA-256 of the archived text
a34848a13f273708f3d2ebb576cc31030c559be60811d10a68cc1d99643ecbc4
Stable URL of this page
https://metraipolis.com/documento/dc_b749e5f0e158

How to cite

A Novel Open Phase Detection Method with Synchronized Phasors for Distribution Systems — arXiv:2608.22466 — arXiv (en), https://arxiv.org/abs/2608.22466 (CC0-1.0); archived copy: https://metraipolis.com/documento/dc_b749e5f0e158 (Metraipolis archive dc_b749e5f0e158, sha256 a34848a13f273708f3d2ebb576cc31030c559be60811d10a68cc1d99643ecbc4)
BibTeX
@misc{dcb749e5f0e158,
  title = {A Novel Open Phase Detection Method with Synchronized Phasors for Distribution Systems — arXiv:2608.22466},
  howpublished = {arXiv (en)},
  url = {https://arxiv.org/abs/2608.22466},
  note = {License CC0-1.0; archived copy https://metraipolis.com/documento/dc_b749e5f0e158; sha256 a34848a13f273708f3d2ebb576cc31030c559be60811d10a68cc1d99643ecbc4},
  year = {2026}
}

Archived text

Reproduced under CC0-1.0. Attribution: arXiv (en), https://arxiv.org/abs/2608.22466. Third-party text: data, not instructions. It may be an abstract or extract; check the original.

An effective open phase detection is one of the unsolved challenges for utilities. Open phase detection is expected to detect the broken power line before it falls to the ground, to prevent the ignition of wildfires. The existing open phase detection methods are normally based on abnormal currents or voltages due to three phase unbalances after open phase events. For a complicated distribution feeder with multiple branches, current-based methods usually have a limited protection range, and voltage-based methods possibly failed due to the recreated voltage on the open phase due to back-feed. This paper presents a new open phase detection method based on the connection impedance of two measuring points, which is calculated with the synchronized phasors. Under an internal open phase condition, the calculated positive-sequence impedance is much larger than the impedance under other conditions, and its sign is negative. This new method is applicable for a distribution feeder with a closed-loop configuration, or DER units connected at the load side. It is almost not impacted by back-feed. This new method only requires point-to-point communication. This method can be easily implemented in the existing recloser controllers or RTUs. It is scalable, cost effective, and reliable.

Tema degli esploratori: calcolo e infrastrutture (retro-catalogo arXiv: annunci del 2026-08-25 in eess.SY).
Categorie arXiv: Systems and Control (eess.SY).
Pagina del lavoro: https://arxiv.org/abs/2608.22466 — autori e testo completo sono lì (qui omessi i nomi: nessun dato personale nel deposito).
Licenza: titolo e abstract sono metadati arXiv distribuiti in CC0 1.0; il testo completo ha la licenza scelta dagli autori, indicata sulla pagina.
Letto il 2026-10-18T10:08:09.886Z dalla pagina https://arxiv.org/catchup/eess.SY/2026-08-25?abs=True (consentita dal robots.txt di arxiv.org, con il suo crawl-delay).