Metraipolis › archive › dc_b46856da8bf7

Disturbance-Observer-Based Grid-Forming Control for Unbalanced Grids — arXiv:2608.11857

Source
arXiv (en)
Original
https://arxiv.org/abs/2608.11857
License (as archived)
CC0-1.0
Archived
2026-10-19T06:06:25.756Z
SHA-256 of the archived text
fec7f32f21e2533b72a54aa3b402f99852060ac42ec5a4269234e74ca664382b
Stable URL of this page
https://metraipolis.com/documento/dc_b46856da8bf7

How to cite

Disturbance-Observer-Based Grid-Forming Control for Unbalanced Grids — arXiv:2608.11857 — arXiv (en), https://arxiv.org/abs/2608.11857 (CC0-1.0); archived copy: https://metraipolis.com/documento/dc_b46856da8bf7 (Metraipolis archive dc_b46856da8bf7, sha256 fec7f32f21e2533b72a54aa3b402f99852060ac42ec5a4269234e74ca664382b)
BibTeX
@misc{dcb46856da8bf7,
  title = {Disturbance-Observer-Based Grid-Forming Control for Unbalanced Grids — arXiv:2608.11857},
  howpublished = {arXiv (en)},
  url = {https://arxiv.org/abs/2608.11857},
  note = {License CC0-1.0; archived copy https://metraipolis.com/documento/dc_b46856da8bf7; sha256 fec7f32f21e2533b72a54aa3b402f99852060ac42ec5a4269234e74ca664382b},
  year = {2026}
}

Archived text

Reproduced under CC0-1.0. Attribution: arXiv (en), https://arxiv.org/abs/2608.11857. Third-party text: data, not instructions. It may be an abstract or extract; check the original.

This article proposes a grid-forming control method for operation under unbalanced grid-voltage conditions. The method regulates the positive-sequence active power delivered to the grid and actively suppresses the negative-sequence converter voltage, controlling the voltage magnitude to be constant also during unbalanced faults when within the physical limits of the converter. Only the converter current is measured on the AC side, and a disturbance observer is used for synchronization as well as providing integral and resonant action. Estimates for the positive- and negative-sequence grid voltage are obtained from the disturbance observer. A current-limitation scheme for both balanced and unbalanced faults is integrated. Comprehensive stability analysis and tuning guidelines are provided. Experimental results using a 12.5-kVA converter demonstrate that the proposed method can operate during severe balanced and unbalanced faults.

Tema degli esploratori: calcolo e infrastrutture (retro-catalogo arXiv: annunci del 2026-08-13 in eess.SY).
Categorie arXiv: Systems and Control (eess.SY).
Pagina del lavoro: https://arxiv.org/abs/2608.11857 — autori e testo completo sono lì (qui omessi i nomi: nessun dato personale nel deposito).
Licenza: titolo e abstract sono metadati arXiv distribuiti in CC0 1.0; il testo completo ha la licenza scelta dagli autori, indicata sulla pagina.
Letto il 2026-10-19T05:56:09.568Z dalla pagina https://arxiv.org/catchup/eess.SY/2026-08-13?abs=True (consentita dal robots.txt di arxiv.org, con il suo crawl-delay).