Metraipolis › archive › dc_9f63d76b1eb7

Job Class Thermal Intent Aware Liquid Cooling Allocation for AI Data Centers — arXiv:2609.30785

Source
arXiv (en)
Original
https://arxiv.org/abs/2609.30785
License (as archived)
CC0-1.0
Archived
2026-10-08T02:04:51.110Z
SHA-256 of the archived text
042ac3824c61431a0be46b14e4fd586e44aef9385b002a791c9b84166e927318
Stable URL of this page
https://metraipolis.com/documento/dc_9f63d76b1eb7

How to cite

Job Class Thermal Intent Aware Liquid Cooling Allocation for AI Data Centers — arXiv:2609.30785 — arXiv (en), https://arxiv.org/abs/2609.30785 (CC0-1.0); archived copy: https://metraipolis.com/documento/dc_9f63d76b1eb7 (Metraipolis archive dc_9f63d76b1eb7, sha256 042ac3824c61431a0be46b14e4fd586e44aef9385b002a791c9b84166e927318)
BibTeX
@misc{dc9f63d76b1eb7,
  title = {Job Class Thermal Intent Aware Liquid Cooling Allocation for AI Data Centers — arXiv:2609.30785},
  howpublished = {arXiv (en)},
  url = {https://arxiv.org/abs/2609.30785},
  note = {License CC0-1.0; archived copy https://metraipolis.com/documento/dc_9f63d76b1eb7; sha256 042ac3824c61431a0be46b14e4fd586e44aef9385b002a791c9b84166e927318},
  year = {2026}
}

Archived text

Reproduced under CC0-1.0. Attribution: arXiv (en), https://arxiv.org/abs/2609.30785. Third-party text: data, not instructions. It may be an abstract or extract; check the original.

GPU-dense AI data centers need to run on liquid cooling as air simply cannot shed the heat at these power densities. Yet the cooling loops themselves are blind to what workloads are about to run; they crank up flow only after a sensor catches a temperature climb, which can take 30 to 50 seconds. We built Job-Class Thermal Intent (JCTI) to close that window. The scheduler already knows a job is coming and what class it belongs to; JCTI feeds that information straight to the cooling controller so it can stage coolant before the heat shows up. We pulled the thermal signatures for each job class out of MLPerf GPU power traces and tuned arrival patterns against Alibaba cluster data. Over 120 paired Monte Carlo trials the numbers come out to 56.4% fewer thermal violations and 60.2% less cumulative overshoot than a straight PI loop. As AI data centers evolving towards gigawatt grid loads with highly fluctuating power swings, thermally-aware scheduling reduces sudden demand and improves load prediction in grid side. Cooling and scheduling have been running as two separate systems for years despite each one knowing something the other needs, JCTI wires them together.

Tema degli esploratori: calcolo e infrastrutture (retro-catalogo arXiv: annunci del 2026-09-28 in cs.DC).
Categorie arXiv: Distributed, Parallel, and Cluster Computing (cs.DC) ; Performance (cs.PF); Systems and Control (eess.SY).
Pagina del lavoro: https://arxiv.org/abs/2609.30785 — autori e testo completo sono lì (qui omessi i nomi: nessun dato personale nel deposito).
Licenza: titolo e abstract sono metadati arXiv distribuiti in CC0 1.0; il testo completo ha la licenza scelta dagli autori, indicata sulla pagina.
Letto il 2026-10-08T01:40:22.286Z dalla pagina https://arxiv.org/catchup/cs.DC/2026-09-28?abs=True (consentita dal robots.txt di arxiv.org, con il suo crawl-delay).