Metraipolis › archive › dc_99f7087150e9

Benefits of Dynamic Thermal Rating for Distribution Transformers Under Accelerated Load Growth — arXiv:2609.36223

Source
arXiv (en)
Original
https://arxiv.org/abs/2609.36223
License (as archived)
CC0-1.0
Archived
2026-10-07T20:48:54.728Z
SHA-256 of the archived text
210641c74c66cae0c9a63750fce29ab699de34d0ebc6b94e13c6862417b4ed69
Stable URL of this page
https://metraipolis.com/documento/dc_99f7087150e9

How to cite

Benefits of Dynamic Thermal Rating for Distribution Transformers Under Accelerated Load Growth — arXiv:2609.36223 — arXiv (en), https://arxiv.org/abs/2609.36223 (CC0-1.0); archived copy: https://metraipolis.com/documento/dc_99f7087150e9 (Metraipolis archive dc_99f7087150e9, sha256 210641c74c66cae0c9a63750fce29ab699de34d0ebc6b94e13c6862417b4ed69)
BibTeX
@misc{dc99f7087150e9,
  title = {Benefits of Dynamic Thermal Rating for Distribution Transformers Under Accelerated Load Growth — arXiv:2609.36223},
  howpublished = {arXiv (en)},
  url = {https://arxiv.org/abs/2609.36223},
  note = {License CC0-1.0; archived copy https://metraipolis.com/documento/dc_99f7087150e9; sha256 210641c74c66cae0c9a63750fce29ab699de34d0ebc6b94e13c6862417b4ed69},
  year = {2026}
}

Archived text

Reproduced under CC0-1.0. Attribution: arXiv (en), https://arxiv.org/abs/2609.36223. Third-party text: data, not instructions. It may be an abstract or extract; check the original.

Dynamic Thermal Rating (DTR) has been widely applied to transmission lines for congestion management, but its potential for distribution transformers is less explored. By adjusting equipment ratings based on real ambient and operating conditions, DTR allows transformers to operate above conservative static nameplate values without compromising asset health. This paper evaluates how DTR can serve as a non-wires alternative to traditional upgrades in distribution systems facing accelerated load growth. Using an example feeder from the SMART-DS dataset, we compare conventional transformer replacement strategies against DTR-enabled operation with ambient-adjusted ratings. The results demonstrate that DTR can defer a significant number of transformer upgrades and reduce annual upgrade costs. More broadly, DTR is most effective in regions with pronounced weather diversity, peak demand occurring during cooler periods, or sustained load growth that would otherwise trigger costly reinforcements. These findings show that DTR is a practical and cost-effective option for utilities, provides both operational flexibility and investment deferral opportunities, and offers a foundation for developing distribution-level DTR programs.

Tema degli esploratori: calcolo e infrastrutture (retro-catalogo arXiv: annunci del 2026-09-30 in eess.SY).
Categorie arXiv: Systems and Control (eess.SY).
Pagina del lavoro: https://arxiv.org/abs/2609.36223 — autori e testo completo sono lì (qui omessi i nomi: nessun dato personale nel deposito).
Licenza: titolo e abstract sono metadati arXiv distribuiti in CC0 1.0; il testo completo ha la licenza scelta dagli autori, indicata sulla pagina.
Letto il 2026-10-07T20:07:11.910Z dalla pagina https://arxiv.org/catchup/eess.SY/2026-09-30?abs=True (consentita dal robots.txt di arxiv.org, con il suo crawl-delay).