Metraipolis › archive › dc_79e9fc3a53a0

Comparative Assessment of Frequency Scans using EMT and RMS Models — arXiv:2608.26851

Source
arXiv (en)
Original
https://arxiv.org/abs/2608.26851
License (as archived)
CC0-1.0
Archived
2026-10-17T22:17:24.286Z
SHA-256 of the archived text
d5f67e3872eca8d96c4c2ba0d8acbef56be37ac6a8a02e31e5f9cdae0007ddc8
Stable URL of this page
https://metraipolis.com/documento/dc_79e9fc3a53a0

How to cite

Comparative Assessment of Frequency Scans using EMT and RMS Models — arXiv:2608.26851 — arXiv (en), https://arxiv.org/abs/2608.26851 (CC0-1.0); archived copy: https://metraipolis.com/documento/dc_79e9fc3a53a0 (Metraipolis archive dc_79e9fc3a53a0, sha256 d5f67e3872eca8d96c4c2ba0d8acbef56be37ac6a8a02e31e5f9cdae0007ddc8)
BibTeX
@misc{dc79e9fc3a53a0,
  title = {Comparative Assessment of Frequency Scans using EMT and RMS Models — arXiv:2608.26851},
  howpublished = {arXiv (en)},
  url = {https://arxiv.org/abs/2608.26851},
  note = {License CC0-1.0; archived copy https://metraipolis.com/documento/dc_79e9fc3a53a0; sha256 d5f67e3872eca8d96c4c2ba0d8acbef56be37ac6a8a02e31e5f9cdae0007ddc8},
  year = {2026}
}

Archived text

Reproduced under CC0-1.0. Attribution: arXiv (en), https://arxiv.org/abs/2608.26851. Third-party text: data, not instructions. It may be an abstract or extract; check the original.

Frequency scans of inverter and grid impedances are crucial for assessing small-signal stability and system strength in inverter-dominated power systems. This paper compares frequency-scan results for several generating units, including a synchronous generator, grid-following, and grid-forming inverters, using fully dq electromagnetic transient and root-mean-square (RMS) models in Simulink. The scans are performed for the same device rating and operating point. Frequency scans and time-domain simulations show that the RMS models are valid only at low frequencies. We find that the current-controlled grid-forming inverter is more difficult to represent in RMS than the voltage-controlled grid-forming inverter. However, including the inner voltage-control loops improves the accuracy of the RMS representation. The paper also investigates the influence of generator and grid impedance on the total system impedance seen from the point of common coupling and relates the oscillatory modes and zeros of the system to peaks and dips in the first and second singular values of the system impedance, respectively.

Tema degli esploratori: calcolo e infrastrutture (retro-catalogo arXiv: annunci del 2026-08-28 in eess.SY).
Categorie arXiv: Systems and Control (eess.SY).
Pagina del lavoro: https://arxiv.org/abs/2608.26851 — autori e testo completo sono lì (qui omessi i nomi: nessun dato personale nel deposito).
Licenza: titolo e abstract sono metadati arXiv distribuiti in CC0 1.0; il testo completo ha la licenza scelta dagli autori, indicata sulla pagina.
Letto il 2026-10-17T22:17:01.661Z dalla pagina https://arxiv.org/catchup/eess.SY/2026-08-28?abs=True (consentita dal robots.txt di arxiv.org, con il suo crawl-delay).