Metraipolis › archive › dc_79e5a8ac8e38

Exploiting the Benefits of V2B Application on Peak Shaving of Data Center Loads — arXiv:2609.00204

Source
arXiv (en)
Original
https://arxiv.org/abs/2609.00204
License (as archived)
CC0-1.0
Archived
2026-10-17T07:33:35.284Z
SHA-256 of the archived text
8cf3f17c60ac08b921c55a402fec94cf89c33cd3384525524a578a9677adc4be
Stable URL of this page
https://metraipolis.com/documento/dc_79e5a8ac8e38

How to cite

Exploiting the Benefits of V2B Application on Peak Shaving of Data Center Loads — arXiv:2609.00204 — arXiv (en), https://arxiv.org/abs/2609.00204 (CC0-1.0); archived copy: https://metraipolis.com/documento/dc_79e5a8ac8e38 (Metraipolis archive dc_79e5a8ac8e38, sha256 8cf3f17c60ac08b921c55a402fec94cf89c33cd3384525524a578a9677adc4be)
BibTeX
@misc{dc79e5a8ac8e38,
  title = {Exploiting the Benefits of V2B Application on Peak Shaving of Data Center Loads — arXiv:2609.00204},
  howpublished = {arXiv (en)},
  url = {https://arxiv.org/abs/2609.00204},
  note = {License CC0-1.0; archived copy https://metraipolis.com/documento/dc_79e5a8ac8e38; sha256 8cf3f17c60ac08b921c55a402fec94cf89c33cd3384525524a578a9677adc4be},
  year = {2026}
}

Archived text

Reproduced under CC0-1.0. Attribution: arXiv (en), https://arxiv.org/abs/2609.00204. Third-party text: data, not instructions. It may be an abstract or extract; check the original.

The accelerated growth in data center projects has introduced a demand-driven bottleneck throughout power grids and contributed to a substantial increase in carbon emissions. These concerns are fueling discussions on methods to use existing energy assets to drive operational efficiency. To this end, this paper explores the benefits of Vehicle-to-Building (V2B) applications to support peak shaving of data center cooling loads. Initially, a literature review was conducted considering V2B constraints and optimization methods including SoC limitations, EV participation, tariffs, and building loads. This analysis was then used to develop a conceptual case study of a 10 MW data center in Loudoun County, VA by simulating a temperature-dependent load profile and adjusting the V2B participation of 40 commercial and passenger EVs. Simulation results indicate that, depending on seasonal variations in cooling load demands, strategic deployment of V2B assets between 12-5pm can offset gross cooling loads by 13-36%.

Tema degli esploratori: calcolo e infrastrutture (retro-catalogo arXiv: annunci del 2026-09-02 in eess.SY).
Categorie arXiv: Systems and Control (eess.SY).
Pagina del lavoro: https://arxiv.org/abs/2609.00204 — autori e testo completo sono lì (qui omessi i nomi: nessun dato personale nel deposito).
Licenza: titolo e abstract sono metadati arXiv distribuiti in CC0 1.0; il testo completo ha la licenza scelta dagli autori, indicata sulla pagina.
Letto il 2026-10-17T07:23:10.000Z dalla pagina https://arxiv.org/catchup/eess.SY/2026-09-02?abs=True (consentita dal robots.txt di arxiv.org, con il suo crawl-delay).