Metraipolis › archive › dc_79067b29682e

Centrality-based Structural-Electrical Contingency Screening and Transmission Reinforcement Prioritization — arXiv:2610.10999

Source
arXiv (en)
Original
https://arxiv.org/abs/2610.10999
License (as archived)
CC0-1.0
Archived
2026-10-09T07:13:37.141Z
SHA-256 of the archived text
84aaf435b8662da775f2868c84945f8a31db1f35fe96aebea01eccef3d8d03bf
Stable URL of this page
https://metraipolis.com/documento/dc_79067b29682e

How to cite

Centrality-based Structural-Electrical Contingency Screening and Transmission Reinforcement Prioritization — arXiv:2610.10999 — arXiv (en), https://arxiv.org/abs/2610.10999 (CC0-1.0); archived copy: https://metraipolis.com/documento/dc_79067b29682e (Metraipolis archive dc_79067b29682e, sha256 84aaf435b8662da775f2868c84945f8a31db1f35fe96aebea01eccef3d8d03bf)
BibTeX
@misc{dc79067b29682e,
  title = {Centrality-based Structural-Electrical Contingency Screening and Transmission Reinforcement Prioritization — arXiv:2610.10999},
  howpublished = {arXiv (en)},
  url = {https://arxiv.org/abs/2610.10999},
  note = {License CC0-1.0; archived copy https://metraipolis.com/documento/dc_79067b29682e; sha256 84aaf435b8662da775f2868c84945f8a31db1f35fe96aebea01eccef3d8d03bf},
  year = {2026}
}

Archived text

Reproduced under CC0-1.0. Attribution: arXiv (en), https://arxiv.org/abs/2610.10999. Third-party text: data, not instructions. It may be an abstract or extract; check the original.

Rapid contingency screening is essential for secure transmission system operation and planning. Although full AC contingency analysis provides accurate system assessment, it requires high computational effort for large contingency sets. Topology-based screening methods reduce this burden but may not accurately represent operating-point-dependent electrical stress. In addition, conventional single-contingency screening does not quantify interactions among simultaneous outages or provide a direct criterion for reinforcement prioritization. This paper presents a hybrid structural-electrical screening approach that combines a computationally efficient, dispatch-independent structural analysis based on reactance-weighted centrality measures with a flow-based severity assessment using line outage distribution factors. Two indices are evaluated using the flow-based severity: a synergy index to quantify super-additive interactions among simultaneous line outages and a tolerance index to rank reinforcement candidates based on their reduction in aggregate post-contingency severity. The correspondence between structural indicators and electrical severity is evaluated quantitatively. Tests on the IEEE 39-bus system identify 115 super-additive line pairs beyond a 5% threshold, with the most severe interaction exceeding seven times the linear combination of individual outage effects. The highest-ranked reinforcement reduces the mean post-contingency thermal severity by 7.5%. The structural rankings show limited correlation with flow-based severity, with a Spearman coefficient of approximately 0.2. The proposed approach provides an efficient pre-screening method to reduce contingency and reinforcement search spaces before detailed AC and economic evaluations.

Tema degli esploratori: calcolo e infrastrutture (elenco arXiv eess.SY, nuovi lavori del giorno).
Categorie arXiv: Systems and Control (eess.SY).
Pagina del lavoro: https://arxiv.org/abs/2610.10999 — autori e testo completo sono lì (qui omessi i nomi: nessun dato personale nel deposito).
Licenza: titolo e abstract sono metadati arXiv distribuiti in CC0 1.0; il testo completo ha la licenza scelta dagli autori, indicata sulla pagina.
Letto il 2026-10-09T07:07:42.923Z dalla pagina https://arxiv.org/list/eess.SY/new (consentita dal robots.txt di arxiv.org, con il suo crawl-delay).