Safety Screening for Voltage Control in Active Distribution Grids via Distributionally Robust Conformal Screening — arXiv:2608.30889

Source
arXiv (en)
Original
https://arxiv.org/abs/2608.30889
License (as archived)
CC0-1.0
Archived
2026-10-17T07:55:03.543Z
SHA-256 of the archived text
08d39b63046b4b08aba70db60cdff0b37dbfabab5eeb20b7f45fa81ae5f45462
Stable URL of this page
https://metraipolis.com/documento/dc_6318802d9539

How to cite

Safety Screening for Voltage Control in Active Distribution Grids via Distributionally Robust Conformal Screening — arXiv:2608.30889 — arXiv (en), https://arxiv.org/abs/2608.30889 (CC0-1.0); archived copy: https://metraipolis.com/documento/dc_6318802d9539 (Metraipolis archive dc_6318802d9539, sha256 08d39b63046b4b08aba70db60cdff0b37dbfabab5eeb20b7f45fa81ae5f45462)
BibTeX
@misc{dc6318802d9539,
  title = {Safety Screening for Voltage Control in Active Distribution Grids via Distributionally Robust Conformal Screening — arXiv:2608.30889},
  howpublished = {arXiv (en)},
  url = {https://arxiv.org/abs/2608.30889},
  note = {License CC0-1.0; archived copy https://metraipolis.com/documento/dc_6318802d9539; sha256 08d39b63046b4b08aba70db60cdff0b37dbfabab5eeb20b7f45fa81ae5f45462},
  year = {2026}
}

Archived text

Reproduced under CC0-1.0. Attribution: arXiv (en), https://arxiv.org/abs/2608.30889. Third-party text: data, not instructions. It may be an abstract or extract; check the original.

Deploying a new control policy for voltage control in active distribution grids requires evidence that physical limits will be satisfied before the policy is tested on the physical grid. This assessment is difficult for two reasons. First, simulations cannot capture every disturbance, modeling error, and device interaction present in the real grid. Second, historical measurements reflect operation under existing control policies, whereas a new policy may drive the grid into different operating conditions. To address these challenges, we propose Distributionally Robust Conformal Safety Screening (DR-CSS), a policy-agnostic framework for pre-deployment, scenario-by-scenario screening of a new control policy using historical data and a nominal simulator. For each new scenario, the simulator predicts a future voltage trajectory for the whole grid; DR-CSS then constructs a conformal safety interval around this prediction using historical simulation-to-reality errors. The interval is further enlarged to account for closed-loop changes induced by the deployment of the new policy and its interactions with the remaining controllers. To the best of our knowledge, DR-CSS is the first framework in power systems to combine historical data from an existing control policy with an imperfect simulator for pre-deployment safety screening of a new policy. Experiments on the IEEE 33-bus and IEEE 141-bus systems evaluate the deployment of learning-based voltage control policies and show that DR-CSS identifies all unsafe test scenarios. To reduce unnecessary warnings on safe scenarios, we adapt the safety intervals to different operating conditions and gradually introduce new policies with recalibration after each stage. These extensions increase the informational value of the safety screening and support safer deployment decisions in active distribution grids.

Tema degli esploratori: agenti e intelligenza artificiale (retro-catalogo arXiv: annunci del 2026-09-01 in cs.AI).
Categorie arXiv: Systems and Control (eess.SY) ; Artificial Intelligence (cs.AI); Machine Learning (cs.LG).
Pagina del lavoro: https://arxiv.org/abs/2608.30889 — autori e testo completo sono lì (qui omessi i nomi: nessun dato personale nel deposito).
Licenza: titolo e abstract sono metadati arXiv distribuiti in CC0 1.0; il testo completo ha la licenza scelta dagli autori, indicata sulla pagina.
Letto il 2026-10-17T07:28:26.921Z dalla pagina https://arxiv.org/catchup/cs.AI/2026-09-01?abs=True (consentita dal robots.txt di arxiv.org, con il suo crawl-delay).