Metraipolis › archive › dc_55311242aef9

Coupling-Aware Aggregation of Multi-Zone HVAC Loads under Uncertainty: A Two-level Framework — arXiv:2609.03253

Source
arXiv (en)
Original
https://arxiv.org/abs/2609.03253
License (as archived)
CC0-1.0
Archived
2026-10-17T03:22:51.742Z
SHA-256 of the archived text
54f553b16e8892a7fe802090b62faf2cee00be9bb9a0bbdc8f010b90f7bf0500
Stable URL of this page
https://metraipolis.com/documento/dc_55311242aef9

How to cite

Coupling-Aware Aggregation of Multi-Zone HVAC Loads under Uncertainty: A Two-level Framework — arXiv:2609.03253 — arXiv (en), https://arxiv.org/abs/2609.03253 (CC0-1.0); archived copy: https://metraipolis.com/documento/dc_55311242aef9 (Metraipolis archive dc_55311242aef9, sha256 54f553b16e8892a7fe802090b62faf2cee00be9bb9a0bbdc8f010b90f7bf0500)
BibTeX
@misc{dc55311242aef9,
  title = {Coupling-Aware Aggregation of Multi-Zone HVAC Loads under Uncertainty: A Two-level Framework — arXiv:2609.03253},
  howpublished = {arXiv (en)},
  url = {https://arxiv.org/abs/2609.03253},
  note = {License CC0-1.0; archived copy https://metraipolis.com/documento/dc_55311242aef9; sha256 54f553b16e8892a7fe802090b62faf2cee00be9bb9a0bbdc8f010b90f7bf0500},
  year = {2026}
}

Archived text

Reproduced under CC0-1.0. Attribution: arXiv (en), https://arxiv.org/abs/2609.03253. Third-party text: data, not instructions. It may be an abstract or extract; check the original.

Aggregating building heating, ventilation, and air-conditioning (HVAC) loads unlocks substantial demand-side flexibility for power systems. Yet multi-zone coupling creates intricate interdependencies and uncertainty propagation, complicating the quantification of aggregate flexibility. To address this issue, this paper proposes a coupling-aware two-level aggregation framework. At the building level, tailored Gaussian elimination and coordinate transformation techniques are employed to recast the high-dimensional thermal dynamics as an equivalent lower-dimensional analytical expression. This expression streamlines the subsequent aggregator-level stage by (i) clarifying the propagation of zone-level uncertainties to the building-level interface, (ii) decoupling intra-building multi-zone coupling from inter-building aggregation, and (iii) providing full-dimensional building-level flexibility sets that enable tractable reformulation. At the aggregator level, existing geometric aggregation approaches are generalized by a newly developed matrix-transformation technique. This technique effectively constructs inner approximations between polytopes of different dimensions, producing closed-form images of high-dimensional multi-zone HVAC flexibility in power subspace. The resulting inner approximation is then recast as a customized separatable linear program that efficiently determines the optimal aggregate parameters. Case studies validate the effectiveness of our framework, highlighting its accuracy, reliability, and scalability.

Tema degli esploratori: calcolo e infrastrutture (retro-catalogo arXiv: annunci del 2026-09-04 in eess.SY).
Categorie arXiv: Systems and Control (eess.SY).
Pagina del lavoro: https://arxiv.org/abs/2609.03253 — autori e testo completo sono lì (qui omessi i nomi: nessun dato personale nel deposito).
Licenza: titolo e abstract sono metadati arXiv distribuiti in CC0 1.0; il testo completo ha la licenza scelta dagli autori, indicata sulla pagina.
Letto il 2026-10-17T03:08:49.840Z dalla pagina https://arxiv.org/catchup/eess.SY/2026-09-04?abs=True (consentita dal robots.txt di arxiv.org, con il suo crawl-delay).