EMT Assessment of SCR and X/R Effects on Current-Priority-Dependent LVRT Response of a Grid-Following BESS — arXiv:2610.41212

Source
arXiv (en)
Original
https://arxiv.org/abs/2610.41212
License (as archived)
CC0-1.0
Archived
2026-11-03T08:32:39.152Z
SHA-256 of the archived text
96266334cc50cd7d56a077d7076ecd8490cd0841f04a57f0f8cbbccbc5c1c540
Stable URL of this page
https://metraipolis.com/documento/dc_53d41dc6e803

How to cite

EMT Assessment of SCR and X/R Effects on Current-Priority-Dependent LVRT Response of a Grid-Following BESS — arXiv:2610.41212 — arXiv (en), https://arxiv.org/abs/2610.41212 (CC0-1.0); archived copy: https://metraipolis.com/documento/dc_53d41dc6e803 (Metraipolis archive dc_53d41dc6e803, sha256 96266334cc50cd7d56a077d7076ecd8490cd0841f04a57f0f8cbbccbc5c1c540)
BibTeX
@misc{dc53d41dc6e803,
  title = {EMT Assessment of SCR and X/R Effects on Current-Priority-Dependent LVRT Response of a Grid-Following BESS — arXiv:2610.41212},
  howpublished = {arXiv (en)},
  url = {https://arxiv.org/abs/2610.41212},
  note = {License CC0-1.0; archived copy https://metraipolis.com/documento/dc_53d41dc6e803; sha256 96266334cc50cd7d56a077d7076ecd8490cd0841f04a57f0f8cbbccbc5c1c540},
  year = {2026}
}

Archived text

Reproduced under CC0-1.0. Attribution: arXiv (en), https://arxiv.org/abs/2610.41212. Third-party text: data, not instructions. It may be an abstract or extract; check the original.

Low-voltage ride-through (LVRT) forces a grid-following inverter to allocate finite converter current between active- and reactive-current objectives. This paper uses a PSCAD electromagnetic-transient (EMT) representation of an aggregated battery energy storage system (BESS) to quantify how short-circuit ratio (SCR) and grid impedance X/R ratio alter that tradeoff. Active-current priority and reactive-current priority are compared for five paired grid conditions under the same 150-ms balanced three-phase fault, with pre-fault active power approximately 0.84 pu, POI reactive-power exchange near 0 pu, and a 1.0-pu dq-current limit. Fundamental positive-sequence voltage and power are reconstructed from 100-$\mu$s three-phase EMT outputs. Across the fixed-fault SCR sweep, the Q-priority late-fault voltage advantage increases from 0.046 pu in the strongest tested grid to 0.129 pu in the weakest; the weakest P-priority case also shows active-power reversal and a pronounced controller-frequency excursion. At fixed SCR, changing X/R produces a smaller increase from 0.092 to 0.112 pu, mainly through reduced P-priority voltage support. Because the common physical fault also deepens the passive retained-voltage condition as SCR decreases, the SCR result is interpreted as a fixed-fault grid-strength sensitivity rather than a constant-sag comparison. Grid strength is the larger sensitivity in the tested matrix, while X/R remains an additional modifier under the studied fault conditions.

Tema degli esploratori: calcolo e infrastrutture (elenco arXiv eess.SY, nuovi lavori del giorno).
Categorie arXiv: Systems and Control (eess.SY).
Pagina del lavoro: https://arxiv.org/abs/2610.41212 — autori e testo completo sono lì (qui omessi i nomi: nessun dato personale nel deposito).
Licenza: titolo e abstract sono metadati arXiv distribuiti in CC0 1.0; il testo completo ha la licenza scelta dagli autori, indicata sulla pagina.
Letto il 2026-11-03T08:15:24.224Z dalla pagina https://arxiv.org/list/eess.SY/new (consentita dal robots.txt di arxiv.org, con il suo crawl-delay).