Metraipolis › archive › dc_305227e0127d
Quantifying Grid-Forming Requirements for System Strength: How Much and Where? — arXiv:2610.08948
- Source
- arXiv (en)
- Original
- https://arxiv.org/abs/2610.08948
- License (as archived)
- CC0-1.0
- Archived
- 2026-10-08T14:17:04.293Z
- SHA-256 of the archived text
59268123cbeec31ba8f5bf1b5338f18624a95dc2c8c7882500183ec554d68ccf- Stable URL of this page
https://metraipolis.com/documento/dc_305227e0127d
How to cite
Quantifying Grid-Forming Requirements for System Strength: How Much and Where? — arXiv:2610.08948 — arXiv (en), https://arxiv.org/abs/2610.08948 (CC0-1.0); archived copy: https://metraipolis.com/documento/dc_305227e0127d (Metraipolis archive dc_305227e0127d, sha256 59268123cbeec31ba8f5bf1b5338f18624a95dc2c8c7882500183ec554d68ccf)
BibTeX
@misc{dc305227e0127d,
title = {Quantifying Grid-Forming Requirements for System Strength: How Much and Where? — arXiv:2610.08948},
howpublished = {arXiv (en)},
url = {https://arxiv.org/abs/2610.08948},
note = {License CC0-1.0; archived copy https://metraipolis.com/documento/dc_305227e0127d; sha256 59268123cbeec31ba8f5bf1b5338f18624a95dc2c8c7882500183ec554d68ccf},
year = {2026}
}Archived text
Reproduced under CC0-1.0. Attribution: arXiv (en), https://arxiv.org/abs/2610.08948. Third-party text: data, not instructions. It may be an abstract or extract; check the original.
As power systems transition toward inverter-based resource (IBR)-dominated grids, Grid-ForMing (GFM) IBRs are increasingly expected to provide the voltage-source characteristics required to maintain adequate system strength. However, how many GFM IBRs are required, and where they should be located in the grid, remains unclear. This paper investigates the impact of the number and location of GFM IBRs on small-signal system strength. The Jacobian Voltage Stiffness Metric (JVSM), which quantifies the voltage-magnitude and voltage-phase stiffness from frequency-domain Jacobian characteristics, is used as a system-strength measure. The analysis demonstrates that increasing the number of GFM IBRs generally improves system strength; however, configurations with the same number of GFM IBRs can exhibit significantly different bus-wise system-strength characteristics depending on their locations. Thus, this paper provides a quantitative basis for specifying GFM requirements in terms of the resulting system strength, rather than solely in terms of penetration level or the number of GFM IBRs. Case studies on a modified IEEE 39-bus system demonstrate how JVSM can be used to quantify and compare the system-strength impact of different numbers and locations of GFM IBRs, with the resulting strength assessments validated against small-signal oscillatory stability. Tema degli esploratori: calcolo e infrastrutture (elenco arXiv eess.SY, nuovi lavori del giorno). Categorie arXiv: Systems and Control (eess.SY). Pagina del lavoro: https://arxiv.org/abs/2610.08948 — autori e testo completo sono lì (qui omessi i nomi: nessun dato personale nel deposito). Licenza: titolo e abstract sono metadati arXiv distribuiti in CC0 1.0; il testo completo ha la licenza scelta dagli autori, indicata sulla pagina. Letto il 2026-10-08T13:28:30.533Z dalla pagina https://arxiv.org/list/eess.SY/new (consentita dal robots.txt di arxiv.org, con il suo crawl-delay).