Multi-Timescale Deliverability of Shared Hybrid Storage for AI Data Center Campuses — arXiv:2610.41249

Source
arXiv (en)
Original
https://arxiv.org/abs/2610.41249
License (as archived)
CC0-1.0
Archived
2026-11-03T06:00:34.956Z
SHA-256 of the archived text
194d162be55c4c51455c45ae082b3bbcb0c0b1c33a7de6bdc4ab36477076a1f5
Stable URL of this page
https://metraipolis.com/documento/dc_1ddbcaafd26e

How to cite

Multi-Timescale Deliverability of Shared Hybrid Storage for AI Data Center Campuses — arXiv:2610.41249 — arXiv (en), https://arxiv.org/abs/2610.41249 (CC0-1.0); archived copy: https://metraipolis.com/documento/dc_1ddbcaafd26e (Metraipolis archive dc_1ddbcaafd26e, sha256 194d162be55c4c51455c45ae082b3bbcb0c0b1c33a7de6bdc4ab36477076a1f5)
BibTeX
@misc{dc1ddbcaafd26e,
  title = {Multi-Timescale Deliverability of Shared Hybrid Storage for AI Data Center Campuses — arXiv:2610.41249},
  howpublished = {arXiv (en)},
  url = {https://arxiv.org/abs/2610.41249},
  note = {License CC0-1.0; archived copy https://metraipolis.com/documento/dc_1ddbcaafd26e; sha256 194d162be55c4c51455c45ae082b3bbcb0c0b1c33a7de6bdc4ab36477076a1f5},
  year = {2026}
}

Archived text

Reproduced under CC0-1.0. Attribution: arXiv (en), https://arxiv.org/abs/2610.41249. Third-party text: data, not instructions. It may be an abstract or extract; check the original.

Artificial intelligence data center (AIDC) campuses contain sustained power variations and subsecond power fluctuations, requiring both sufficient stored energy and fast response. A shared hybrid energy storage system (HESS) can mitigate aggregate AIDC power deviations, but interval-based schedules cannot capture the delay between commanded and delivered power at the campus point of common coupling (PCC). To this end, this paper proposes a multi-timescale scheduling model for mitigating AIDC power fluctuations with the shared HESS. First, it models electrical pooling at the campus bus and constrains the shared HESS to a single PCC injection. Second, a two-layer model passes five-minute scheduled power, energy state, and reserve capacity to a causal fast response model that distinguishes commanded power from delivered power. Case studies using the National Laboratory of the Rockies (NLR) GenAI Power Profiles Dataset show reductions in both PCC and fast integral absolute error (IAE), while retaining most of the improvement available under ideal response.

Tema degli esploratori: calcolo e infrastrutture (elenco arXiv eess.SY, nuovi lavori del giorno).
Categorie arXiv: Systems and Control (eess.SY).
Pagina del lavoro: https://arxiv.org/abs/2610.41249 — autori e testo completo sono lì (qui omessi i nomi: nessun dato personale nel deposito).
Licenza: titolo e abstract sono metadati arXiv distribuiti in CC0 1.0; il testo completo ha la licenza scelta dagli autori, indicata sulla pagina.
Letto il 2026-11-03T05:42:21.126Z dalla pagina https://arxiv.org/list/eess.SY/new (consentita dal robots.txt di arxiv.org, con il suo crawl-delay).