Metraipolis › archive › dc_15761faef682

Model-Free PID Tuning by Step-Response Inspection — arXiv:2609.15711

Source
arXiv (en)
Original
https://arxiv.org/abs/2609.15711
License (as archived)
CC0-1.0
Archived
2026-10-16T02:58:03.622Z
SHA-256 of the archived text
21ec836f17c6d1ac5e6d45f13aa5cba47bf9b9c5f5013ec6020e93cdbc5dc060
Stable URL of this page
https://metraipolis.com/documento/dc_15761faef682

How to cite

Model-Free PID Tuning by Step-Response Inspection — arXiv:2609.15711 — arXiv (en), https://arxiv.org/abs/2609.15711 (CC0-1.0); archived copy: https://metraipolis.com/documento/dc_15761faef682 (Metraipolis archive dc_15761faef682, sha256 21ec836f17c6d1ac5e6d45f13aa5cba47bf9b9c5f5013ec6020e93cdbc5dc060)
BibTeX
@misc{dc15761faef682,
  title = {Model-Free PID Tuning by Step-Response Inspection — arXiv:2609.15711},
  howpublished = {arXiv (en)},
  url = {https://arxiv.org/abs/2609.15711},
  note = {License CC0-1.0; archived copy https://metraipolis.com/documento/dc_15761faef682; sha256 21ec836f17c6d1ac5e6d45f13aa5cba47bf9b9c5f5013ec6020e93cdbc5dc060},
  year = {2026}
}

Archived text

Reproduced under CC0-1.0. Attribution: arXiv (en), https://arxiv.org/abs/2609.15711. Third-party text: data, not instructions. It may be an abstract or extract; check the original.

Industrial PID loops are still tuned by hand: step the setpoint, look at the response, change a gain. This paper turns that procedure into an algorithm, SPIN, for Step-response Phase-portrait INspection. From a single closed-loop step response we form three phase portraits of the control deviation and count how many times each trajectory winds around its settling point. The counts are dimensionless and independent of the step size and of the clock. They show which channel is under-damped: integral, proportional, or derivative. A triangular rule reads the three counts, cutting the gain of the one band whose fault is certain and raising that of every band the same test shows to be within its limit. No model is identified and no optimization is solved. The iteration is deterministic and its gains stay inside a fixed box. Because a ringing count is itself the evidence that the loop is in the regime where cutting that band's gain reduces the count, the iteration settles into a cycle at the edge of the well-damped set. It needs no excitation beyond a routine setpoint step, so it can run on a process in operation, and it may start from arbitrary gains, including destabilizing ones. SPIN assumes a stable, self-regulating process whose gain and phase both fall with frequency, which covers the lag-plus-dead-time models common in process control, and a controller from the nested family $\mathrm{I} \subset \mathrm{PI} \subset \mathrm{PID}$ with integral action present. We validate it on a battery of process-typical plants with one fixed step size and one set of dimensionless constants throughout. Every decision is visible: the operator sees what the algorithm sees. A reference implementation and an interactive demonstration are public.

Tema degli esploratori: calcolo e infrastrutture (retro-catalogo arXiv: annunci del 2026-09-15 in eess.SY).
Categorie arXiv: Systems and Control (eess.SY) ; Signal Processing (eess.SP).
Pagina del lavoro: https://arxiv.org/abs/2609.15711 — autori e testo completo sono lì (qui omessi i nomi: nessun dato personale nel deposito).
Licenza: titolo e abstract sono metadati arXiv distribuiti in CC0 1.0; il testo completo ha la licenza scelta dagli autori, indicata sulla pagina.
Letto il 2026-10-16T02:45:08.552Z dalla pagina https://arxiv.org/catchup/eess.SY/2026-09-15?abs=True (consentita dal robots.txt di arxiv.org, con il suo crawl-delay).