EMT Assessment of SCR and X/R Effects on Current-Priority-Dependent LVRT Response of a Grid-Following BESS — arXiv:2610.41212
- Source
- arXiv (en)
- Original
- https://arxiv.org/abs/2610.41212
- License (as archived)
- CC0-1.0
- Archived
- 2026-11-02T05:15:30.725Z
- SHA-256 of the archived text
6f7e4954410a850b8d2ab6fe9df4eed8005e9df770078794dd79a83650648a3b- Stable URL of this page
https://metraipolis.com/documento/dc_13b8bddcbaa5
How to cite
EMT Assessment of SCR and X/R Effects on Current-Priority-Dependent LVRT Response of a Grid-Following BESS — arXiv:2610.41212 — arXiv (en), https://arxiv.org/abs/2610.41212 (CC0-1.0); archived copy: https://metraipolis.com/documento/dc_13b8bddcbaa5 (Metraipolis archive dc_13b8bddcbaa5, sha256 6f7e4954410a850b8d2ab6fe9df4eed8005e9df770078794dd79a83650648a3b)
BibTeX
@misc{dc13b8bddcbaa5,
title = {EMT Assessment of SCR and X/R Effects on Current-Priority-Dependent LVRT Response of a Grid-Following BESS — arXiv:2610.41212},
howpublished = {arXiv (en)},
url = {https://arxiv.org/abs/2610.41212},
note = {License CC0-1.0; archived copy https://metraipolis.com/documento/dc_13b8bddcbaa5; sha256 6f7e4954410a850b8d2ab6fe9df4eed8005e9df770078794dd79a83650648a3b},
year = {2026}
}Archived text
Reproduced under CC0-1.0. Attribution: arXiv (en), https://arxiv.org/abs/2610.41212. Third-party text: data, not instructions. It may be an abstract or extract; check the original.
Low-voltage ride-through (LVRT) forces a grid-following inverter to allocate finite converter current between active- and reactive-current objectives. This paper uses a PSCAD electromagnetic-transient (EMT) representation of an aggregated battery energy storage system (BESS) to quantify how short-circuit ratio (SCR) and grid impedance X/R ratio alter that tradeoff. Active-current priority and reactive-current priority are compared for five paired grid conditions under the same 150-ms balanced three-phase fault, with pre-fault active power approximately 0.84 pu, POI reactive-power exchange near 0 pu, and a 1.0-pu dq-current limit. Fundamental positive-sequence voltage and power are reconstructed from 100-$\mu$s three-phase EMT outputs. Across the fixed-fault SCR sweep, the Q-priority late-fault voltage advantage increases from 0.046 pu in the strongest tested grid to 0.129 pu in the weakest; the weakest P-priority case also shows active-power reversal and a pronounced controller-frequency excursion. At fixed SCR, changing X/R produces a smaller increase from 0.092 to 0.112 pu, mainly through reduced P-priority voltage support. Because the common physical fault also deepens the passive retained-voltage condition as SCR decreases, the SCR result is interpreted as a fixed-fault grid-strength sensitivity rather than a constant-sag comparison. Grid strength is the larger sensitivity in the tested matrix, while X/R remains an additional modifier under the studied fault conditions. Tema degli esploratori: calcolo e infrastrutture (elenco arXiv eess.SY, nuovi lavori del giorno). Categorie arXiv: Systems and Control (eess.SY). Pagina del lavoro: https://arxiv.org/abs/2610.41212 — autori e testo completo sono lì (qui omessi i nomi: nessun dato personale nel deposito). Licenza: titolo e abstract sono metadati arXiv distribuiti in CC0 1.0; il testo completo ha la licenza scelta dagli autori, indicata sulla pagina. Letto il 2026-11-02T04:57:58.333Z dalla pagina https://arxiv.org/list/eess.SY/new (consentita dal robots.txt di arxiv.org, con il suo crawl-delay).