Identifiability-Guided Composite Load Modeling of AI Data Centers — arXiv:2610.19565
- Source
- arXiv (en)
- Original
- https://arxiv.org/abs/2610.19565
- License (as archived)
- CC0-1.0
- Archived
- 2026-10-15T15:02:58.872Z
- SHA-256 of the archived text
f0549fce30fc8491f752878375be77c0d963d8b435f519cdd3b7f8995ae7c087- Stable URL of this page
https://metraipolis.com/documento/dc_05ee360be551
How to cite
Identifiability-Guided Composite Load Modeling of AI Data Centers — arXiv:2610.19565 — arXiv (en), https://arxiv.org/abs/2610.19565 (CC0-1.0); archived copy: https://metraipolis.com/documento/dc_05ee360be551 (Metraipolis archive dc_05ee360be551, sha256 f0549fce30fc8491f752878375be77c0d963d8b435f519cdd3b7f8995ae7c087)
BibTeX
@misc{dc05ee360be551,
title = {Identifiability-Guided Composite Load Modeling of AI Data Centers — arXiv:2610.19565},
howpublished = {arXiv (en)},
url = {https://arxiv.org/abs/2610.19565},
note = {License CC0-1.0; archived copy https://metraipolis.com/documento/dc_05ee360be551; sha256 f0549fce30fc8491f752878375be77c0d963d8b435f519cdd3b7f8995ae7c087},
year = {2026}
}Archived text
Reproduced under CC0-1.0. Attribution: arXiv (en), https://arxiv.org/abs/2610.19565. Third-party text: data, not instructions. It may be an abstract or extract; check the original.
The rapid growth of AI data centers introduces large, workload-dependent loads whose protection and reconnection behavior can affect power-system transient stability. Calibrating dynamic models of such loads is challenging because treating all associated elements as freely estimable may lead to weakly identified or physically confounded parameterizations. This paper proposes an identifiability-guided calibration framework for a composite load model with separate IT, cooling, and auxiliary branches. A nuisance-projected Fisher-information criterion characterizes the local identifiability of the cooling-motor composition, while a workload non-equivalence result shows that voltage-only recalibration cannot reproduce workload-dependent responses. Guided by these results, a grey-box estimator trained with branch-level supervision learns the workload-to-power relation and the cooling composition, while retaining a prescribed UPS protection law and an externally anchored reconnect-ramp duration. The learned workload relation is then distilled into a closed form for transient-stability simulation. Evaluation using 300,000 MIT Supercloud GPU power-utilization samples and 12,600 IEEE 39-bus fault scenarios yields an aggregate active-power $R^2$ of 0.948, compared with 0.856 for an LSTM baseline. Removing branch-level supervision preserves relatively high aggregate accuracy but substantially degrades cooling-component recovery. Under unseen deep voltage sags, the proposed model achieves a transient $R^2$ of 0.750, compared with 0.033 for the LSTM. Closed-loop simulations further show that cooling composition and protection behavior can affect retained-load states and voltage responses near protection thresholds. Tema degli esploratori: calcolo e infrastrutture (elenco arXiv eess.SY, nuovi lavori del giorno). Categorie arXiv: Systems and Control (eess.SY). Pagina del lavoro: https://arxiv.org/abs/2610.19565 — autori e testo completo sono lì (qui omessi i nomi: nessun dato personale nel deposito). Licenza: titolo e abstract sono metadati arXiv distribuiti in CC0 1.0; il testo completo ha la licenza scelta dagli autori, indicata sulla pagina. Letto il 2026-10-15T14:07:08.581Z dalla pagina https://arxiv.org/list/eess.SY/new (consentita dal robots.txt di arxiv.org, con il suo crawl-delay).