Metraipolis › archive › dc_05b0d44bb008

A Mixed $H_{\infty}$--Passivity Approach for Leveraging Heat-Pump-Connected District Heating Systems as Frequency Support in Electric Power Systems — arXiv:2610.40955

Source
arXiv (en)
Original
https://arxiv.org/abs/2610.40955
License (as archived)
CC0-1.0
Archived
2026-11-02T05:15:28.908Z
SHA-256 of the archived text
14fe0c9f1381ae83a55e701b4107100f99ca7921847739595f9b025ee6e4ffe7
Stable URL of this page
https://metraipolis.com/documento/dc_05b0d44bb008

How to cite

A Mixed $H_{\infty}$--Passivity Approach for Leveraging Heat-Pump-Connected District Heating Systems as Frequency Support in Electric Power Systems — arXiv:2610.40955 — arXiv (en), https://arxiv.org/abs/2610.40955 (CC0-1.0); archived copy: https://metraipolis.com/documento/dc_05b0d44bb008 (Metraipolis archive dc_05b0d44bb008, sha256 14fe0c9f1381ae83a55e701b4107100f99ca7921847739595f9b025ee6e4ffe7)
BibTeX
@misc{dc05b0d44bb008,
  title = {A Mixed $H_infty$--Passivity Approach for Leveraging Heat-Pump-Connected District Heating Systems as Frequency Support in Electric Power Systems — arXiv:2610.40955},
  howpublished = {arXiv (en)},
  url = {https://arxiv.org/abs/2610.40955},
  note = {License CC0-1.0; archived copy https://metraipolis.com/documento/dc_05b0d44bb008; sha256 14fe0c9f1381ae83a55e701b4107100f99ca7921847739595f9b025ee6e4ffe7},
  year = {2026}
}

Archived text

Reproduced under CC0-1.0. Attribution: arXiv (en), https://arxiv.org/abs/2610.40955. Third-party text: data, not instructions. It may be an abstract or extract; check the original.

Heat-pump (HP)-connected district heating systems (DHSs) can support grid frequency by rapidly modulating HP electrical consumption while accommodating the resulting heat imbalance. Thermal-state-informed HP control improves EPS--DHS coordination, but introduces slower DHS dynamics and heat-side disturbance propagation at the electrical interface on the time scale of secondary frequency control. This paper formulates the regulated DHS as a grid-facing dynamic port and develops a mixed $H_\infty$--passivity framework for disturbance-independent temperature regulation while preserving a clean electrical response during secondary frequency control. Sufficient conditions guarantee local asymptotic stability of the EPS--HP--DHS interconnection across primary frequency control, secondary frequency control, and DHS regulation. These stability conditions are integrated with multi-channel $H_\infty$ attenuation of DHS-state-dependent electrical dynamics, heat-disturbance propagation, and DHS-regulation errors, yielding a tractable convex LMI program for controller synthesis. Cross-model validation deploys controllers synthesized on control-oriented EPS--DHS models, without retuning, on an open-source electromechanical IEEE 39-bus model coupled with four high-fidelity finite-volume DHS models retaining thermal transport, storage, and heat-loss dynamics. The resulting controller improves EPS--DHS coordination without compromising the grid-facing electrical response.

Tema degli esploratori: calcolo e infrastrutture (elenco arXiv eess.SY, nuovi lavori del giorno).
Categorie arXiv: Systems and Control (eess.SY).
Pagina del lavoro: https://arxiv.org/abs/2610.40955 — autori e testo completo sono lì (qui omessi i nomi: nessun dato personale nel deposito).
Licenza: titolo e abstract sono metadati arXiv distribuiti in CC0 1.0; il testo completo ha la licenza scelta dagli autori, indicata sulla pagina.
Letto il 2026-11-02T04:57:58.329Z dalla pagina https://arxiv.org/list/eess.SY/new (consentita dal robots.txt di arxiv.org, con il suo crawl-delay).