Adaptive Grid-Mode-Aware Hybrid Energy Storage Control for AI Data Center Oscillation Mitigation — arXiv:2611.05939

Source
arXiv (en)
Original
https://arxiv.org/abs/2611.05939
License (as archived)
CC0-1.0
Archived
2026-11-05T18:39:48.471Z
SHA-256 of the archived text
94b62f71050d89b007fcd018a11b91ce90f52bb228ef240c4a2ad91908daf431
Stable URL of this page
https://metraipolis.com/documento/dc_0587870a9cda

How to cite

Adaptive Grid-Mode-Aware Hybrid Energy Storage Control for AI Data Center Oscillation Mitigation — arXiv:2611.05939 — arXiv (en), https://arxiv.org/abs/2611.05939 (CC0-1.0); archived copy: https://metraipolis.com/documento/dc_0587870a9cda (Metraipolis archive dc_0587870a9cda, sha256 94b62f71050d89b007fcd018a11b91ce90f52bb228ef240c4a2ad91908daf431)
BibTeX
@misc{dc0587870a9cda,
  title = {Adaptive Grid-Mode-Aware Hybrid Energy Storage Control for AI Data Center Oscillation Mitigation — arXiv:2611.05939},
  howpublished = {arXiv (en)},
  url = {https://arxiv.org/abs/2611.05939},
  note = {License CC0-1.0; archived copy https://metraipolis.com/documento/dc_0587870a9cda; sha256 94b62f71050d89b007fcd018a11b91ce90f52bb228ef240c4a2ad91908daf431},
  year = {2026}
}

Archived text

Reproduced under CC0-1.0. Attribution: arXiv (en), https://arxiv.org/abs/2611.05939. Third-party text: data, not instructions. It may be an abstract or extract; check the original.

Oscillatory power components in AI data-center demand can produce large frequency deviations when they coincide with vulnerable grid modes. Mode-aware hybrid energy storage systems (HESSs) can selectively suppress these components, but their effectiveness degrades when the grid mode changes while the control target remains fixed. This paper proposes a closed-loop grid-mode-adaptive HESS control framework that integrates measurement-based modal identification with mode-selective control. A sliding-window N4SID estimator identifies the local grid dynamics from grid-side power and frequency measurements, and the resulting natural-frequency estimate is used to retune the modal suppression branch assigned to the supercapacitor. The framework is evaluated under a grid-mode shift from 0.50 to 1.35Hz while maintaining equal physical damping and approximately equal load excitation at both frequencies. Compared with the fixed-target controller, the adaptive method reduces the post-change grid-side modal power component from 8.78 to 2.02MW, corresponding to a 76.94% reduction, and substantially lowers the resulting frequency deviation.

Tema degli esploratori: calcolo e infrastrutture (elenco arXiv eess.SY, nuovi lavori del giorno).
Categorie arXiv: Systems and Control (eess.SY).